Measuring Resistance With a Multimeter
Most people mess this up because they skip the prep work. I spent three days chasing a phantom ground fault on a compressor once because I didn't think to disconnect the circuit properly before taking a reading. The problem was just capacitive coupling from an adjacent live wire, but the multimeter didn't care about that distinction. It just gave me a number that looked plausible until I actually traced everything by hand. Here is how you do it right the first time.
How To Check Ohms Correctly
Start by making sure the circuit is dead. This sounds obvious, but I've seen it happen way too often. Use your multimeter in voltage mode first to confirm zero potential across the component you're about to measure. If there's even a few volts sitting on that line, you're going to get garbage readings and you might damage the meter. Some cheaper meters don't have proper overvoltage protection on the ohms range. Plug the black lead into the COM port and the red lead into the port marked with the omega symbol. On most meters that's the rightmost port. If your meter has a separate current port, don't put the red lead there unless you're measuring current. I once blew a fuse on a Fluke 87V because someone had left the leads on the amp port and then measured resistance on a live panel. The meter clicked, smoked slightly, and gave me a reading of zero ohms that made absolutely no sense until I opened it up. Set the dial to the ohms range. Most digital multimeters have an auto-ranging feature these days, so just selecting the resistance function is usually enough. If yours doesn't auto-range, start on the highest scale and work your way down. You want the display to show a value without hitting the OL or overloaded indicator. If it shows OL, you've either got an open circuit or your range is too low.
Touch the probes to the component or circuit point you want to measure. For discrete components like resistors, you should desolder at least one leg so you're not measuring the parallel path through the board. A resistor that reads fifty percent low is almost always being dragged down by surrounding traces or components. I had a board where a 10k pull-up resistor was reading 3.2k because it was in parallel with the input impedance of a transistor base. Took me a while to figure out which leg was lifted when I finally just cut the trace with an X-Acto knife. Write down your reading and the range you used. It sounds tedious but you will forget which setting you were on within an hour if you're checking multiple points. I keep a small notebook now and just jot the reference designator next to each measurement. Takes maybe ten seconds per point.
Get the Full Details

Things That Throw Off Your Readings
Parasitic paths are the main culprit. Whenever you're measuring resistance on a populated circuit board, every component connected in parallel to what you're trying to measure will affect the result. The lower the resistance you're expecting, the more this matters. A 100 ohm reading on a board with a 1k pull-down nearby is going to look like about 83 ohms. If you're working with high resistance values like megohm-range insulation measurements, parallel paths matter less but leakage currents and humidity start becoming significant factors. Temperature affects resistance too. Most resistors have a temperature coefficient, and semiconductors change resistance dramatically with temperature. I once measured a motor winding that read 4.2 ohms at room temperature, then six hours later after the motor had been running, it was reading 5.8 ohms. The nameplate said 5 ohms nominal. That's perfectly normal for copper windings, but if you don't know what to expect you might think something is wrong. Aluminum windings shift even more. Probe resistance is negligible for most measurements but matters when you're checking very low resistances. A pair of decent test leads might add 0.1 to 0.3 ohms depending on condition and contact pressure. For a 0.5 ohm shunt resistor, that's a huge error. Some meters have a relative mode that subtracts the lead resistance. Press the relative button with the probes touching and the display will zero out, then take your measurement. On my current meter it's the button labeled RHOLD or just REL depending on the model.
When Resistance Measurements Lie to You
Semiconductor junctions will fool you. If you put probes across a diode, a transistor base-emitter junction, or an LED, the multimeter's test current might not be enough to forward bias the junction properly, or it might be enough to partially conduct and give you a misleadingly low resistance. I learned this the hard way on a power supply board where I was checking for shorted components and kept getting inconsistent readings across what I thought was a MOSFET drain-source path. The body diode inside the MOSFET was conducting in one direction and blocking in the other, making it look like the device was fine when it was actually partially shorted under load conditions. Switching to diode test mode clarified things immediately because that mode applies a known forward current and shows the voltage drop instead of a resistance calculation. Capacitors also mess with resistance measurements. If you connect probes across a capacitor, the reading will start low and climb toward infinity as the capacitor charges. That's normal behavior for the meter, but if you're expecting a steady resistance value and see a moving number, you might think the component is faulty when it's just a capacitor doing its thing. Discharge capacitors before measuring resistance nearby. A stored charge can also damage your meter's resistance circuitry. Insulation resistance testing requires a different approach entirely. Standard multimeter ohms ranges typically apply only a few hundred millivolts of test voltage, which is nowhere near enough to detect insulation breakdown under operating conditions. If you need to verify insulation integrity on motor windings or cable runs, you need a megohmmeter or insulation tester that applies 500V or 1000V DC. The readings you get from a regular multimeter on insulation will always be misleadingly high because the test voltage is too low to stress the insulation material the way it experiences in service. I had a situation where a motor passed a standard multimeter check at 2 megohms but failed a proper megger test at 0.3 megohms. The insulation was dry on the surface but degraded underneath, and the low test voltage couldn't penetrate that.
Practical Setup Notes
Keep your probes clean. Oxidized probe tips give intermittent contact and variable readings. I carry a small contacts cleaner pen and occasionally run the tips through it. Cheap alligator clip adapters are useful for hands-off measurements but add about 0.05 ohms of resistance per connection due to spring contact resistance. Not a big deal for most work but noticeable when you're measuring low-value shunts or transformer windings. Auto-zero or auto-calibration on higher-end meters can help. The Extech and Fluke meters I've used have this feature. It essentially shorts the inputs internally and zeros out any offset voltage before taking a measurement. Takes about three seconds but eliminates a source of error that's easy to overlook. For three-wire or four-wire resistance measurements, you need a meter that supports Kelvin sensing. This is standard on bench DMMs and process calibrators but rare on handheld meters under five hundred dollars. If you're measuring anything below about one ohm on a production basis, consider whether a four-wire setup is worth the investment. The difference between a good two-wire measurement and a four-wire one at sub-ohm values is the difference between knowing your answer and guessing.

The actual How To Check Ohms process is straightforward once you understand what the meter is doing and what can go wrong. Measure dead circuits, account for parallel paths, use the right tool for the job, and trust your readings only when you understand the limitations of the method you're using.