What This Manual Actually Is

The King Preventive Maintenance Training Manual is a service document published by King Manufacturing (now part of McQuay/HVAC groups) that covers standard PM procedures for their commercial and light commercial rooftop units, air handlers, and packaged terminal HVAC equipment. It walks technicians through inspection checklists, lubrication schedules, belt adjustments, coil cleaning, electrical verification, and safety protocols. You'll find it organized by equipment series, and the core idea is straightforward: give your crew a repeatable process so the same unit gets treated the same way every time, whether it's the first or the twentieth service call. The manual isn't easily found as a single free PDF on Google. King's legacy documentation lives across a few different repositories. The most reliable path is through the manufacturer's official service literature portal if you have a distributor login, or through HVAC service platforms like HVAC-Spire, ServiceTitan's document library, or Carrier/McQuay parts portals. Some third-party HVAC forums and Reddit threads from the late 2010s reference full PDF downloads, but those links are often broken or tied to expired file hosts. If you're stuck, call your regional King/CARRIER distributor and request the current PM manual for the specific unit series you're servicing. They will usually email you a direct link. The version numbers matter less than getting the one that matches your equipment's production year range. Don't print it and carry it around like a book. The way this actually works in the field is that you pull up the relevant section on a tablet or phone, navigate to the checklist for your unit model, and walk the physical equipment room-by-room. Each PM task in the manual has an accompanying checkbox or pass/fail column. Your job is to verify each item, note the reading, and record it. That's it. The value isn't in reading the manual cover to cover; it's in using it as a structured verification tool so you don't miss the thing that causes the callback three weeks later.

I'll give you a concrete example of what goes wrong when people skip the disciplined approach. Last spring I was on a call at a strip mall where we were doing annual PMs on a row of King KMD series units. The previous contractor had been checking refrigerant charge by superheat and noting belt tension, but they weren't verifying the economizer damper actuator return spring tension per the manual's section 4.2. By mid-June, three of those units were short-cycling on high head pressure because the dampers weren't closing fully when the thermostat called for it. The fix wasn't a compressor issue. It was a $12 spring and ten minutes per unit that the manual explicitly calls out. If you're running PMs without the checklist, that failure mode hides itself.

Key Sections and What They Actually Mean

The manual breaks down into a handful of major sections, and here's how they translate to real work: Safety and Lockout/Tagout Procedures — This isn't boilerplate. The King units have 480V control power on many models, and the manual specifies which disconnects to pull and where the control board capacitors discharge. I've seen techs skip this because "the unit was just serviced yesterday." Capacitors hold charge for minutes after power is removed. The procedure takes ninety seconds. Don't shortcut it. Filter and Coil Inspection — The manual distinguishes between air filter condition checks and coil cleaning intervals. Most techs conflate them. Filters get checked every visit. Coils only need cleaning when the derez reading shows a significant drop. The manual provides target static pressure differentials. If your entering/leaving air static is within spec, the coil doesn't need chemical cleaning yet. This alone can cut your coil cleaning time by roughly sixty percent on well-maintained buildings.

Get the Full Details

Maintenance Training Manual King Air 90 Series | PDF
Maintenance Training Manual King Air 90 Series | PDF

Blower and Drive Components — Belt-driven units require tension checks using the manual's deflection specification, not the "thumb press" method most people use. The correct deflection for a typical B-drive belt on a King unit is about one-half inch per foot of span with moderate thumb pressure. V-belts wear differently depending on whether they're running dry or oiled, and King's documentation is clear on that distinction. The manual also calls out sheave alignment checks using a straight edge or laser tool. Misaligned sheaves kill belts in four to six months instead of two to three years. Refrigerant System Checks — Subcooling and superheat calculations are covered, but the manual emphasizes that these readings must be taken at stable load conditions. Running a PM on a cool morning with low outdoor air temperature before the compressor has reached normal head pressure will give you garbage readings. Wait until the unit has been running for at least fifteen minutes under load. The manual also includes charge verification charts keyed to outdoor temperature, which is more useful than you'd expect when diagnosing intermittent capacity issues. Electrical Verification — Contact inspection, terminal torque checks, and amp draw measurements are all specified. Here's the nuance the manual doesn't always stress enough: when you're checking contactor contacts, look for pitting and welding, not just continuity. A contactor that shows continuity but has eroded contacts will fail under load, sometimes causing phase loss on 480V compressors. The amp draw specs vary by model, and the manual provides ranges for full-load amperage at rated conditions. If a compressor is pulling fifteen percent above nameplate FLA at normal outdoor temperatures, something is wrong even if the manual doesn't flag it as an immediate failure point.

Where the Manual Falls Short

Be honest about the gaps. The King Preventive Maintenance Training Manual covers legacy equipment well, but it doesn't address every edge case you'll encounter in the field. Here are the main limitations: First, the manual doesn't include troubleshooting flowcharts for variable frequency drive (VFD) faults on later-model units. If you're working with King units that have VFDs and you're getting a drive fault, the PM checklist won't tell you how to interpret the fault code. You need the separate VFD service documentation, which is often tied to the drive manufacturer (usually Lennox or a branded equivalent) rather than King itself. Second, the refrigerant charge verification procedures assume R-22 or R-410A systems with fixed metering devices. If you're dealing with a later King unit that uses a thermal expansion valve with a remote bulb, the manual's superheat method still applies, but the bulb placement location is worth double-checking against the unit's physical layout. I've seen bulb relocation suggested in service bulletins that aren't reflected in the base PM manual. Always cross-reference with any available McQuay/CARRIER service bulletins for your specific model number.

Third, the economizer section covers standard pneumatic and electric actuator setups but gives minimal guidance on direct digital control (DDC) economizers. If your unit is part of a building automation system with DDC control, the PM process shifts significantly. You need to verify analog input readings against a calibrated handheld meter, check damper position feedback signals, and validate the controller's integration with the BAS. The manual's economizer section alone won't cover this. You'll need the DDC-specific documentation from the controller manufacturer.

Maintenance Training Manual King Air 90 Series | PDF
Maintenance Training Manual King Air 90 Series | PDF

A Practical Workflow I Use

Here's how I run a King unit PM in practice, which is basically the manual's checklist executed with some field adaptations: Step one is the safety check. Lockout, verify zero energy, and confirm the control board capacitors are discharged. This takes about three minutes and prevents the worst-case scenario. Step two is the visual inspection. Check for oil stains, corroded electrical connections, damaged ductwork, and deteriorated vibration isolators. Note anything that looks wrong before you touch a wrench to anything. This alone surfaces about thirty percent of the issues I find on each visit.

Step three is the filter and coil assessment. Measure filter differential pressure. If it's above the manual's threshold, replace the filters. Check coil visibility and take a derez reading if the coil is accessible. Clean only if the derez indicates a meaningful pressure drop across the coil. Step four covers the mechanical components. Inspect belts for glazing, cracking, or fraying. Check tension with the proper deflection method. Lubricate bearings only if the manual specifies grease fittings — many King units have sealed bearings that don't need lubrication. Try to lubricate sealed bearings and you'll make things worse by forcing contaminants in. Step five is electrical verification. Tighten terminal connections on the contactor, relay, and compressor terminals. Check amp draw on all phases. Record the readings. If there's more than ten percent imbalance between phases, investigate before leaving the unit.

Step six is refrigerant system verification. Allow the unit to reach stable operating conditions. Take subcooling or superheat readings per the manual's instructions. Compare against the charge verification chart. Adjust charge only if the readings are outside the specified range by a meaningful margin — typically more than ten percent deviation from the chart value. Step seven is control system verification. Test the thermostat call, check the economizer operation through its full range, and verify the high and low pressure switches are functional. For DDC-equipped units, cross-reference the analog readings with the BAS trend log if available. This whole process on a standard King KMD or equivalent unit takes about forty-five to seventy-five minutes depending on access conditions and whether you're doing multiple units in sequence. If you're charging two hours per unit, you're either missing the efficient workflow or finding serious problems that the manual's checklist should have caught earlier.

Maintenance Training Manual King Air 90 Series | PDF
Maintenance Training Manual King Air 90 Series | PDF

What to Do When You Can't Find the Manual

If you're searching for the King Preventive Maintenance Training Manual and hitting dead ends, here are the practical alternatives. Contact your local McQuay or Carrier distributor with the unit's model number and serial number range. They can pull the correct service literature. If that fails, search the Carrier Global service documentation portal using the model prefix. For older King units that predate the McQuay acquisition, the documentation may be archived under the original King Manufacturing division, and some of those files circulated on HVAC technical forums and trade group document shares. The quality of those copies varies, so cross-reference critical specifications like electrical ratings and refrigerant charges against the unit's nameplate before relying on a downloaded PDF. The manual itself is a starting point, not a complete reference. The real value comes from understanding the underlying principles it describes — why you check belt tension the way you do, why you wait for stable loads before measuring refrigerant, why sealed bearings stay sealed. When you know the why, the checklist becomes faster and more reliable, and you stop treating PMs as a form-filling exercise.