What actually happens when you take a relay training course
Most people go into protection relay training expecting to learn how to pick settings and push buttons. The reality is more tedious than that. You spend half the course learning company standards, the other half arguing about whether a particular CT ratio is adequate for a given fault current. The useful stuff is in the middle somewhere. I spent three days in a classroom once where the instructor opened the session by asking everyone what they wanted to get out of it. About six different answers, none of them matching. By Friday, we had covered distance elements, overcurrent pickup ranges, and the annoying habit engineers have of ignoring coordination margins because "it'll be fine in practice." It wasn't fine in practice. Not on that particular feeder anyway. But that's a separate story.
Protection Relay Training Courses That Actually Matter
The courses worth your time share a few traits. They use real relays, not slides of relays. You get hands-on time setting up a trip curve, not just watching someone else do it. And they teach you what to do when the software refuses to accept your coordination file because two time dial settings are within 0.02 seconds of each other and the algorithm flags a false merge. I went through a program at ETDP back in 2014 that was decent for fundamentals. The instructors had field experience instead of just reading from manuals. More recent ones have gotten better at using actual SEL and ABB hardware in the lab. The cheap online courses are okay for brushing up on terminology but worthless for learning how to actually commission a protective scheme. You can watch a video all day and still not know why your ground overcurrent element is picking up on capacitive charging current during a perfectly healthy system condition.
What you should actually be able to do after training
Here's a realistic checklist. After a solid course you should be able to read an IEC 61850 communication mapping file without immediately needing someone to translate it for you. You should understand the difference between IEC 60255 and NERC C12.24 without confusing the two standards. You should be able to pull a setting group from a relay, compare it to a baseline, and explain what changed. Most importantly you should know how to verify that your CT saturation calculations match what the relay actually sees during a fault. CT saturation is where most newly trained engineers get burned. You size the CT based on standard burden tables, run the study, everything looks fine. Then a real fault happens and the CT saturates within two cycles because you used the symmetrical RMS current for sizing instead of the asymmetrical peak including the DC offset. A good course will make you work through this scenario with actual oscillography data. A bad one will show you a diagram and move on to lunch.
Get the Full Details

How to evaluate a course before enrolling
Check the syllabus carefully. If it doesn't mention coordination studies, fault analysis methodology, or relay testing procedures, skip it. Look for courses that include a lab component with actual troubleshooting scenarios. You want to be handling real faults, not simulated textbook ones with clean sinusoidal waveforms. The industry-standard paths right now tend to cluster around a few providers. EPRI runs regular sessions that cover transmission and distribution applications thoroughly. IEEE Power & Energy Society has localized workshops. Some relay manufacturers like SEL and GE run their own programs which are useful if you're dealing with their hardware specifically, though the methodology they teach isn't always transferable to other platforms. I took a course once that was almost entirely focused on one brand of relay. Useful if you work for a utility that only uses that brand, pretty much useless if you change jobs. Make sure the curriculum covers principles that apply across manufacturers. Distance element characteristics, differential percentages, directional ground overcurrent logic. Those don't change based on who built the case around the microprocessor.
A specific problem I ran into and how training helped
I was commissioning a double busbar configuration with a breaker and a half scheme. The training course I'd taken covered busbar differential elements but only in a generic context. When I got to the actual site, the relay manufacturer had implemented the busbar differential using a synthesized busbar current approach rather than individual bay current summation. The settings manual described the generic method. It didn't address the synthesized approach at all. I spent two days trying to make the coordination work because the busbar relay was tripping on external faults. The root cause was that the CT ratios on the bus coupler breaker were mismatched with the bay CTs in a way that created a small but persistent differential current under load. The relay's percentage restraint curve wasn't set high enough to handle it. A more experienced engineer pointed out that the issue was the CT ratio selection during the design phase, not the relay settings themselves. We ended up adjusting the restraint slope and adding a blocking element based on rate of change of frequency to prevent nuisance tripping during heavy load transfers between buses. That situation wasn't covered in any training course I'd attended. But the foundational knowledge from those courses let me understand what was happening when I looked at the oscillography. I could read the waveform, identify that the differential element was seeing residual current, and trace it back to the CT mismatch. Without the basics you just stare at the screen and wait for someone more senior to tell you what to do next.
Common pitfalls even trained engineers fall into
One thing I see repeatedly is people trusting coordination software output without manual verification. The software will happily give you a coordination file that looks perfect until you realize it's coordinating two elements that aren't actually in series on the network. Another is overlooking the impact of generator inrush current on overcurrent element settings. You set the pickup based on maximum load current plus a safety margin, then the generator comes online and the inrush trips your downstream element because you didn't account for the transient. Time grading studies are another area where training helps but also where practice matters more. The theory is straightforward. You set upstream elements with a longer time delay than downstream elements to ensure selectivity. The practice involves dealing with breaker operating time tolerances, relay timing errors, and the fact that digital relays sometimes report inaccurate operating times at the extreme ends of their range. I've seen relays claim a 40 millisecond operating time on a 5P class CT at 20 times rated current when the actual time was closer to 65 milliseconds. The relay was functioning correctly according to its own measurement methodology, just not in the way you expected.

What to expect practically
Most full courses run three to five days. Online options exist but the quality varies enormously. A good in-person course will cost anywhere from two thousand to five thousand dollars depending on the provider and depth. Some employers cover this. Others expect you to pay for it yourself as part of professional development. Factor in travel time if the course isn't local. A three-day course with travel and hotel comes out to about five days of your life minimum. If you're working with medium voltage distribution systems the training needs are different from someone doing EHV transmission work. Distribution protection is heavier on overcurrent coordination and recloser settings. Transmission protection brings in distance elements, pilot schemes, and more complex communication-based schemes. Make sure the course you choose matches your actual application area rather than giving you a broad overview that doesn't dig deep enough into either.
Alternatives when formal training isn't available
Not everyone has the budget or time for a week-long course. In those situations the next best thing is working directly with experienced colleagues on live projects. There's no substitute for watching someone walk through a coordination study from start to finish and explaining the decisions along the way. Reading manufacturer application guides helps too, though those are written for engineers who already understand the fundamentals. Open source tools like CYMTRAP and some of the newer Python-based coordination frameworks can fill gaps. They're not as polished as commercial solutions but they force you to understand the underlying calculations rather than treating the software as a black box. I've used them to verify coordination files from commercial tools and found errors in about one out of every ten studies. Usually minor issues but occasionally significant enough to affect system security. Relay test sets are another area where hands-on experience beats classroom learning. Learning to use a relay test set properly takes more time than any course can provide. You need to understand injection techniques, the difference between step and continuous test modes, and how to interpret the results when your test equipment doesn't quite match the relay's measurement methodology. This is something you develop over months of actual use, not in a single training session.